Labels: ,

Case Study - Slough Police Station

Airtherm Engineering has completed another installation using Nova commercial product serving two existing Potteron Derwent atmosperic boilers & one Hamworthy water heater at Slough Police station.

Nova is a new breed of chimney system that offers a single solution for virtually all of today's combustion requirements. The system is a true multi-fuel / multi-application product - whether being used to serve a solid fuel stove, vent the latest high efficiency condensing appliances or Biomass wood chip / pellet stove, Nova is the product of choice.

Nova boasts a diameter range covering thirteen sizes and covers domestic and commercial applications. Manufactured from a 316L inner liner, 25mm high density insulated annulus and a grade 304 outer case, Nova is built to last.

Client: Perfect Pipework Ltd

Sector: Public
Products: MasterFlue System
Equipment: Potterton Derwent 
                     Hamworthy DR-LA40
Application: Atmosperic


• Boilers: Potterton Derwent
• Water Heater: Hamworthy DR-LA40
• Application: Chimney / Flue system
• Operating mode: Dry
• Pressure: Negative / Positive pressure
• Working pressure: 200 Pa (product will operate 1000pa max)
• Inner wall: 316L1.4404/1.457 thickness Ø500 1 mm
• Outer wall: AISI 304/ 1.4301 thickness 0,6 mm
• Insulation: 25mm thick Rockwool insulation
• Sealant : Tri-lip 'o' type silicone ring
• Fuel type: Gas
• Suitable for fully condensing applications
• Fully welded construction
• High level insulation
• High thermal resistance
• High speed twist lock jointing system to aid installation
• Without seals the product is suitable for multi fuel applications up to 450°C

Diameters: 100mm - 600mm


Construction: Twin Wall Insulated


Material: 316L stainless steel liner and 304 stainless steel outer case


Temperature: 450°C Continuous without seals 200°C with seals fitted

 
Pressure capability: 200Pa (P1)


Mode of operation: Negative or positive pressure
 

Approvals:
BS EN 1856-1 T460 N1 D V2 L50050 G(50) Nova SM
BS EN 1856-1 T600 N1 D V2 L50050 G(50) Nova SF
BS EN 1856-1 T200 P1 W V2 L50050 O(50) Nova SM c/w seals


For more information: www.airtherm.co.uk