Case Study - Mansion Studios, Nottingham

Chimney and flue specialist Airtherm Engineering Limited was appointed, in August 2012, as the preferred flue installer at a new Mansion Studios refurbishment in the City Centre of Nottingham.

Bowman House is an existing 1970’s, 4-storey office building which has been converted into 140 one-bed studios for students. The building is now known as Mansion Studios. 
 
The brief was to design, supply and install two twin wall stainless steel insulated flue systems, each serving high efficiency heatmaster boilers and a chp unit, all located in the basement of the building.


The boiler house was extremely congested and gave our installation team a challenging time, but due to their experience we overcame the obstacle's and completed on-time.

Both systems complying with BS & Clean Air Act Memorandum.

Consultant
Clancy Consulting

Client
MVS Limited

Sector
Education

Products
Dinak DWHp

Equipment

3 x Heatmaster 85T

1 x ENER-G E25 CHP
 

Application
Condensing



Boilers: Heatmaster 85T 
 

CHP:  ENER-G E25
 

Model: Modulex 1 x 290kw &  2 x 900kw
 

Application:  Chimney / Flue system
 

Operating mode: Dry / Wet  
 

Pressure: Negative Pressure
 

Working pressure: 200 Pa (product will operate 1000pa max)     
 

Inner wall: 316L1.4404/1.457 thickness
 

Outer wall: AISI 304/ 1.4301 thickness 0,5
 

Insulation: 30mm thick Rockwool insulation
 

Sealant: Tri-lip 'o' type silicone ring 
 

Fuel type: Gas        

For more information: www.airtherm.co.uk